| Model Number (Reverse Cycle) | Packaged Unit | P048AHR |
|
Rated Cooling
|
Total Capacity (kW)3 | 45.84 |
| Sensible3 | 38.09 | |
| EER (kW/ikW)3 | 3.16 | |
|
Rated Heating1
|
Total Capacity (kW) | 47.48 |
| COP | 3.65 | |
| MEPS Certified | Yes | |
|
Operating Range
|
Maximum °C | 50 |
| Minimum °C | -10 | |
| Capacity Steps | % | 0/50/100 |
|
Compressor
|
Type | Tandem Scroll |
| Starter | D.O.L (Optional Soft Starter) | |
| Qty | 1 | |
|
Outdoor Fan
|
Type | EC Axial |
| Speed Control | Pressure Transducer | |
| Qty | 1 | |
|
Refrigerant System
|
Type | R410A |
| Charge Per Circuit kg | 10.8 | |
| No of Circuits | 1 | |
|
Indoor Fan
|
Type | EC Plug |
| Speed Control | Potentiometer | |
| Qty | 1 | |
|
Airflow Indoor (L/s)
|
Nominal | 2470 |
| Maximum | 3088 | |
| Minimum | 1853 | |
| Available External Static Pressure |
Pa | High Static Capability (See Performance Curves) |
| IP Rating | IP44 | |
| Power Supply | (Volt/Phase/Hz) | 400-415V / 3Ph + N / 50Hz |
| Rated Load Amps4. | Total | 26.6 |
| Full Load Amps5. | Total | 38.2 |
|
Total
Dimensions (mm) |
Height | 1760 |
| Width | 1550 | |
| Length | 1850 | |
| Nominal Weight2. | Total kg | 570 |
| Rated Sound Power | db(A) | 68.5 |
Apac P048AHR 45.84 kW Signature Compact Rooftop Package Unit
45.84 kW Cooling | 47.48 kW Heating
Apac P048AHR 45.84 kW Signature Compact Rooftop Package Unit
- 35% smaller footprint than equivalent RTU
- 25% less gas charge than equivalent RTU
- 42% less components than equivalent RTU
5 Year Manufacturer’s Warranty
Features
- Tandem scoll compressors for high system efficiency at full & part load
- 35% smaller footprint than equivalent RTU
- 25% less gas charge than equivalent RTU
- 42% less components than equivalent RTU
- EC plug fans with high static capability up to 500pa
- EC hybrid axial fan
- TXV refrigerant control
- Condenser coil anti-corrosion protection
- Open controls
- 25mm PE closed cell insulation
- Phase fail protection relay
- MEPS certified
Factory options customised to order
- Compressor soft starter
- High static pressure outdoor fans
- Double layered insulation to indoor section
- Capacity modulation control
- Outdoor coil(s) with anti-corrosion post-treatment
- Indoor coil(s) with anti-corrosion post-treatment
- Outdoor coil guards, powder coated
- Discharge & suction isolation valves
- Liquid line isolation valves across filter drier
- Cable markers
- Fire relay
- APAC Supply & Return connections
- High Level Interface (HLI) Modbus connectivity
- Integrated filter frame 50mm
- Economiser – dampers and actuators (no controls)
Factory options engineered to order
- 316 stainless steel cabinet, unpainted
- 304 stainless steel cabinet, powder coated
- Stainless steel external fixings
- Outdoor coil(s) copper / copper
- Indoor coil(s) copper / copper
- Power supply – no neutral (415/3/50)
- Ductable air off in lieu of standard axial