Model Number (Reverse Cycle)
|
Indoor Unit | S015ILR |
| Outdoor Unit | S015OVR | |
|
Rated Cooling
|
Total Capacity (kW)3 | 15.54 |
| Sensible3 | 12.13 | |
| EER (kW/ikW)3 | 3.7 | |
|
Rated Heating1
|
Total Capacity (kW) | 14.7 |
| COP | 3.87 | |
| MEPS Certified | Yes | |
|
Operating Range
|
Maximum °C | 50 |
| Minimum °C | -10 | |
| Capacity Steps | % | 0/100 |
|
Compressor
|
Type | Scroll |
| Starter | D.O.L (Optional Soft Starter) | |
| Qty | 1 | |
|
Outdoor Fan
|
Type | Hybrid Axial |
| Speed Control | Pressure Transducer | |
| Qty | 2 | |
|
Refrigerant System
|
Type | R410A |
| Charge Per Circuit kg | 5.3 | |
| No of Circuits | 1 | |
|
Indoor Fan
|
Type | EC Centrifugal Blower |
| Speed Control | Variable Speed | |
| Qty | 1 | |
|
Airflow Indoor (L/s)
|
Nominal | 835 |
| Maximum | 1044 | |
| Minimum | 626 | |
| Available External Static Pressure |
Pa | +200 Pa |
| IP Rating | IP44 | |
| Power Supply | (Volt/Phase/Hz) | 400-415V / 3Ph + N / 50Hz |
| Rated Load Amps4 | Outdoor/Indoor/ Total |
7.5/ 2.8/ 11.3 |
| Full Load Amps5 | Outdoor/Indoor/ Total |
12/4.4/16.4 |
|
Outdoor Dimensions (mm)
|
Height | 1162 |
| Width | 730 | |
| Length | 1550 | |
|
Indoor Dimensions (mm)
|
Height | 444 |
| Width | 1225 | |
| Length | 655 | |
|
Indoor and Outdoor Pipe Connection Diameter
|
Liquid mm (inch) | 9.5 (3/8″) x 1 |
| Gas mm (inch) | 19.1 (3/4″) x 1 | |
| Nominal Weight 2. | Outdoor kg | 214 |
| Nominal Weight 2. | Indoor kg | 70 |
|
Rated Sound Power
|
db(A)
|
61.7
|
1. For reverse cycle model only
2. For base model only. Factory options will vary
3. Performance excludes ikW of evaporator fan motor
4. R.L.A – Run Load Amps are based on current drawn at nominal conditions
5. F.L.A – Full Load Amps are based on the overload settings [max current] of all compressor and fan motor(s)