| CAPACITY | 14.0kW | |||
| Set | FDT140AVNXWVH | |||
| Indoor | FDT140VH | |||
| Outdoor | FDCA140VNX-W | |||
| Power Source (Outdoor Unit) | 1 Phase 240V 50Hz | |||
|
*Operation Data
|
Nominal Capacity (Range)
|
Cooling T1 |
kW
|
14.0 (3.5-16.0) |
| Heating H1 | 16.0 (2.7-18.0) | |||
| Heating H2 | 15.5 | |||
|
Power Consumption
|
Cooling T1 | 3.87 | ||
| Heating H1 | 4.2 | |||
| Maximum Power Consumption | 7.1 | |||
|
Running Current
|
Cooling T1 |
A
|
17 | |
| Heating H1 | 18.3 | |||
| Inrush Current, Maximum Current | 5, 27 | |||
| EER | Cooling T1 | 3.62 | ||
| COP | Heating H1 | 3.81 | ||
| Sound Power Level (JIS C9612) | Outdoor |
dB(A)
|
69 | |
|
Sound Pressure Level (JIS C9612)
|
Indoor | P-Hi:48 Hi:42 Me:39 Lo:32 | ||
| Outdoor | 54 | |||
|
External dimensions (HXWXD)
|
Indoor |
mm
|
298x840x840 | |
| Panel | 35x950x950 T-PSAE-5BW-E (Fine Snow) / T-PSAE-5BB-E (Shadow Black) | |||
| Outdoor | 1300x970x370 | |||
|
Net weight
|
Indoor |
kg
|
Unit 25 Panel 5 | |
| Outdoor | 97 | |||
|
Airflow
|
Cooling (Indoor) |
l/s
|
P-Hi: 633 Hi:483
Me: 433 Lo:317 |
|
| Heating (Indoor) | ||||
|
Installation Data
|
Refrigerant (R32)
|
Quantity | kg | 4 |
| Pre-Charged to Pipe | m | 30 | ||
|
Refrigerant Piping
|
Liquid Line |
mm
|
Ø9.52 | |
| Gas Line | Ø15.88 | |||
| Connection Method | Flare Connection | |||
| Maximum Pipe Length (One Way) |
m
|
100 | ||
| Max Vertical Height Diff. Between O.U. and I.U. | 50 ( O.U. above I.U. ) / 15 ( O.U. below I.U. ) | |||
| Controller | RC-E5, RC-EXZ3A, RCH-E3 or RCN-T-5BW-E2 (Fine Snow) / RCN-T-5BB-E2 (Shadow Black) | |||
| Motion Sensor (Optional) | LB-T-5BW-E (Fine Snow) / LB-T-5BB-E (Shadow Black) | |||
| Demand Response (AS4755) | Yes | |||
|
Outdoor air temperature (upper, lower limits)
|
Cooling |
oC
|
-15 to 50 | |
| Heating | -20 to 20 | |||