| Technical Information | PACKAGE UNIT | |
| PACKAGE / OUTDOOR MODEL |
PKV720T
|
|
| INDOOR MODEL | ||
|
(1) Total (Gross) Capacity (kW) (AS/NZS3823.1.2)
|
Cooling (Rated) | 73.25 |
| Heating (Rated) | 71.25 | |
|
Net (Rated) Capacity (kW) (AS/NZS3823.1.2)
|
Cooling (Rated) | 24.00 / 71.50 / 78.65 |
| Heating (Rated) | 23.20 / 73.00 / 80.30 | |
|
Input Power (kW) (AS/NZS3823.1.2)
|
Cooling (Min / Rated / TruMax) | 21.25 |
| Heating (Min / Rated / TruMax) | 22 | |
|
Input Power (kW) Tru-max
|
Cooling (Rated) | 24.35 |
| Heating (Rated) | 25.9 | |
|
(2) EER Rated (AS/NZS3823.1.2)
(3) COP Rated (AS/NZS3823.1.2) |
Cooling (Rated) | 3.45 |
| Heating (Rated) | 3.1 | |
| EER Tru-max | Cooling (Tru-max) | 3.23 |
| COP TRU-MAX | Heating (Tru-max) | 3.1 |
|
Seasonal Performance Factor Commercial
|
TCSPF (Hot / Mixed / Cold) | 4.76 / 4.75 / 5.03 |
| HSPF (Hot / Mixed / Cold) | – | |
|
Power Supply – (V / Ph / Hz)
|
Package / Outdoor | 400V / 3PH + N- / 50Hz |
| Indoor | – | |
| Rated Amps (AS/NZS3823.1.2) | 33.6 | |
| Full Load Amps (AS/NZS3823.1.2) Outdoor / Indoor / Total | 47.0 / 6.0 / 53.0 | |
| Circuit Breaker Amps (Suggested) | 63 | |
|
IP Rating
|
Outdoor | IP44 |
| Indoor | IP20 | |
|
Compressor
|
Type / No. per Unit | Inverter Variable Speed Scroll / 2 |
| Starting Method | Inbuilt Soft Starting | |
| No. of refrigeration Circuits / No. Capacity Stages | 2 / Variable Capacity | |
| Refrigerant | R-410A | |
|
Fans (Type x Number per units)
|
Outdoor | Variable Speed ECM / Direct Drive Axial Fan x 2 |
| Indoor | Variable Speed ECM / Direct Drive Backward Curve Plug Fan x 1 (72kW), 2 (85kW & 96kW) | |
|
Airflow Indoor (l/s)
|
Maximum | 4500 |
| Nominal | 3800 | |
| Minimum | 1000 | |
|
Package / Outdoor Dimensions (mm)
|
Depth | 2710 |
| Height | 1910 | |
| Width | 2375 | |
|
Indoor Dimensions (mm)
|
Depth | – |
| Height | – | |
| Width | – | |
|
Nominal Weight (kgs)
|
Outdoor | 1096 |
| Indoor | – | |
| Sound Pressure Level (dBA) | Outdoor (Quiet / Rated / Tru-Max) | 63.6 / 70.2 / 70.2 |
| Sound Power Level (dBA) | Outdoor (Quiet / Rated / Tru-Max) | 80.6 / 87.2 / 87.2 |
| MEPS Certified | Yes | |
ActronAir PKV720T 73.25kW Variable Speed Commercial Rooftop Package Unit
73.25 kW Cooling | 71.25 kW Heating
ActronAir PKV720T 73.25kW Variable Speed Commercial Rooftop Package Unit
Tru-Inverter Technology Variable Speed | Energy Efficiency | Insulated Performance
Description
73.25 kW Cooling
71.25 kW Heating