| CAPACITY | 16.0KW | |||
| Set | FDUA160AVNXWVH | |||
| Indoor | FDUA160VH | |||
| Outdoor | FDCA160VNX-W | |||
| Power Source (Outdoor Unit) | 1 Phase 240V 50Hz | |||
|
*Operation Data
|
Nominal Capacity Range
|
Cooling T1 |
kW
|
16.0 (5.0-17.0) |
| Heating H1 | 18.0 (4.0-21.0) | |||
| Heating H2 | 15 | |||
|
Power Consumption
|
Cooling T1 | 5 | ||
| Heating H1 | 5 | |||
| Max Power Consumption | 7.1 | |||
|
Running Current
|
Cooling T1 |
A
|
22 | |
| Heating H1 | 22 | |||
| Inrush Current, Maximum Current | 5, 30 | |||
| EER | Cooling T1 | 3.16 | ||
| COP | Heating H1 | 3.6 | ||
| Sound Power Level (JS C9612) | Outdoor |
dB(A)
|
69 | |
|
Sound Pressure Level (JS C9612)
|
Indoor | P-Hi:48 Hi:47 Me:43 Lo:41 | ||
| Outdoor | 54 | |||
|
External Dimensions (HXWXD)
|
Indoor |
mm
|
398x1450x930 | |
| Outdoor | 1300x970x370 | |||
|
Net Weight
|
Indoor |
Kg
|
66 | |
| Outdoor | 97 | |||
| Supply Air Connection |
mm
|
298×1064 | ||
| Return Air Connection | 2 X Ø400 | |||
| External Static Pressure (Max) | Pa | 150 | ||
|
Airflow
|
Indoor (Cooling) |
l/s
|
P-Hi:1000 Hi:867 Me:733 Lo:683 | |
| Indoor (Heating) | P-Hi:1000 Hi:867 Me:733 Lo:600 | |||
|
Refrigerant (R32)
|
Quantity | kg | 4 | |
| Pre Charged To Pipe Length |
m | 30 | ||
|
Installation Data
|
Refrigerant Piping
|
Liquid Line |
mm
|
Ø9.52 |
| Gas Line | Ø15.88 | |||
| Connection Method | ||||
| Maximum Pipe Length (One Way) |
m
|
100 | ||
| Max vertical height diff. between O.U. and I.U. | Max^50 (O.U above I.U Outdoor temp ≤ 43°C) , Max 30 (O.U above I.U Outdoor temp > 43°C) / 15 (O.U below I.U) | |||
| Controller | ||||
| Safety Pan (Optional) | N/A | |||
| Motion Sensor (Optional) | ||||
| Demand response (AS4755) | Yes | |||
|
Outdoor air temperature (upper, lower limits)
|
Cooling |
oC
|
-15 to 50 | |
| Heating | -20 to 20 | |||