| CAPACITY | 7.1 KW | |||
| Set | FDU71AVNXWVH | |||
| Indoor | FDU71VH | |||
| Outdoor | FDCA71VNX-W | |||
| Power Source (Outdoor Unit) | 1 Phase 240V 50Hz | |||
|
*Operation Data
|
Nominal Capacity Range
|
Cooling T1 |
kW
|
7.1 (3.2-8.0) |
| Heating H1 | 8.0 (3.6-9.0) | |||
| Heating H2 | 7.4 | |||
|
Power Consumption
|
Cooling T1 | 1.77 | ||
| Heating H1 | 1.78 | |||
| Max Power Consumption | 4.11 | |||
|
Running Current
|
Cooling T1 |
A
|
7.9 | |
| Heating H1 | 7.9 | |||
| Inrush Current, Maximum Current | 5, 20 | |||
| EER | Cooling T1 | 4.01 | ||
| COP | Heating H1 | 4.49 | ||
| Sound Power Level (JS C9612) | Outdoor |
dB(A)
|
66 | |
|
Sound Pressure Level (JS C9612)
|
Indoor | P-Hi:38 Hi:33 Me:29 Lo:25 | ||
| Outdoor | 51 | |||
|
External Dimensions (HXWXD)
|
Indoor |
mm
|
280x950x635 | |
| Outdoor | 750×880(+88)x340 | |||
|
Net Weight
|
Indoor |
Kg
|
34 | |
| Outdoor | 60 | |||
| Supply Air Connection |
mm
|
170×880 | ||
| Return Air Connection | 200X740 | |||
| External Static Pressure (Max) | Pa | 200 | ||
|
Airflow
|
Indoor (Cooling) |
l/s
|
P-Hi:400 Hi:316 Me: 250 Lo:166
|
|
| Indoor (Heating) | ||||
|
Refrigerant (R32)
|
Quantity | kg | 2.75 | |
| Pre Charged To Pipe Length |
m | 30 | ||
|
Installation Data
|
Refrigerant Piping
|
Liquid Line |
mm
|
Ø9.52 |
| Gas Line | Ø15.88 | |||
| Connection Method | Flare Connection | |||
| Maximum Pipe Length (One Way) |
m
|
50 | ||
| Max vertical height diff. between O.U. and I.U. | 30 ( O.U. above I.U.) / 15 ( O.U. below I.U. ) |
|||
| Controller | RC-E5, RC-EXZ3A, RCH-E3 or RCN-KIT4-E2 | |||
| Motion Sensor (Optional) | LB-KIT2 | |||
| Demand response (AS4755) | Yes | |||
|
Outdoor air temperature (upper, lower limits)
|
Cooling |
oC
|
-15 to 50 | |
| Heating | -20 to 20 | |||